# A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

Input Types | 输入类型

In order for the system to know how to react when an input is triggered, it needs to be given an input type.

 

为了能让系统知道当输入被触发后如何反应,需要给它一个输入类型

 

The table below shows all the different input types that can be selected. For the UK and International markets, some of the input types have be renamed however, their functions are identical.

 

UK

International

Description

Unused

Unused

Factory default. Input is programmed out of operation.

Fire

Fire

Active at all times. Audible response: Full (differentiated). Communicator: ‘Fire’ signal.

Gas

Gas

Active at all times. Audible response: Full (differentiated) Communicator: ‘Gas’ signal.

HU

PA

Active at all times. Audible Response: Full (differentiated) Communicator: ‘Hold Up’ and ‘Input HU’ signals.

Silent HU

Silent PA

Active at all times. Audible Response: None Communicator: ‘Hold Up’ and ‘Input HU’ signals.

Tamper

Tamper

When unset: Audible Response: Internal only Communicator: ‘Tamper’ signal. When set: Audible Response: Full (differentiated). Communicator: ‘Tamper'.

Intruder

Instant

Active when set. Audible Response: Full Communicator: ‘Intruder’ and ‘Unconfirmed’ signals.

Final Exit

Entry Delay 1

Active when set – initiates entry timer, if system not unset before entry time expires: Audible Response: Full. Communicator: ‘Intruder’ and ‘Unconfirmed’ signals.

Entry Route

Follow

Active when set, except during entry time. Audible Response: Full. Communicator: ‘Intruder’ and ‘Unconfirmed’ signals.

ER

(Area FX)

N/A

(For use with level sets). When fully set, acts as 'Entry Route' input, as above. When part set, acts as 'Final Exit' input, as above.

FX

(Area ER)

N/A

(For use with level sets). When fully set, acts as 'Final Exit' input, as above. When part set, acts as 'Entry Route' input, as above.

PTS

Push To Arm

Active during exit time to complete setting procedure. No audible or communicator response.

PLEASE NOTE: May be used to act as ‘doorbell’ by use of ‘chime’ attribute.

Switcher

Switcher

Active at all times. No audible or communicator response triggers associated output or switches other equipment.

Day Alarm

24 Hour

When set: Audible Response: Full. Communicator: ‘Intruder’ and ‘Unconfirmed’ signals. When unset: Audible Response: Programmable. Communicator: ‘Day Alarm’ signal.

Ward Control

 

Input is allocated by system software and cannot be reprogrammed to a different type, though relevant attributes may be adjusted.

Fault

Fault

Active when unset. Audible Response: Graduated internally Triggers ‘Global Fault 1’ outputs if the system is set. Triggers ‘Global Fault 2’ output if the system is set/unset.

Closure Supervision

Arming Control

Active during Setting procedure. No audible or communicator response. Prevents system being set whilst active.

Shunt Input

Shunt

Active at all times. No audible or communicator response Accepts input from keyswitch (or equivalent) to shunt the inputs assigned to it. Associated outputs are available. After 10 seconds the detectors in the shunt list will be active.

Unset Input

Disarm Only

Active when set. Accepts input from keyswitch (or equivalent) to Unset the Area/Level set assigned to it.

Keyswitch Latched

Keyswitch Latched

Accepts input from keyswitch (or equivalent) to Set/Unset the Set modes assigned to it. Setting includes normal exit time, etc. Requires latching action switch. PLEASE NOTE: Does not comply with grade 2 or grade 3.

Entry Shock Input

Entry Shock

Active when system set. Works in conjunction with 'Final Exit' input type for detection of forced entry.

Input Line Fail

Line Fault

Active when fail. Will give a line fault alarm, and will signal telecom line fault signal on expiry of line fault timer. Works in conjunction with CCTV input.

Keyswitch Pulsed

Keyswitch Pulsed

Accepts input from keyswitch (or equivalent) to set/unset the set modes assigned to it. Requires momentary action switch to toggle set/unset state.

PLEASE NOTE: Does not comply with grade 2 or grade 3.

Interior

interior

This will work the same as an Intruder type input, the only difference is that when CID reporting is programmed then any inputs that are programmed as 'Interior' will report CID event 132.

Flood

Flood

This input type will work as a 24 hour input, any inputs that are programmed for 'Flood' will activate the external siren and will report CID event 113.

CCTV

CCTV

Active at all times. No audible or communicator response If the input line fail is active, the system will signal CID/SIA events for perimeter alarm and the CCTV input will open.

Perimeter

Perimeter

This will work the same as an Intruder type input, the only difference is that when CID reporting is programmed then any inputs that are programmed as 'Perimeter' will report CID event 131.

Keybox

Patrol / Keybox

This input type will work similar to a switcher input, it does not trigger an alarm but will report CID event 250 and is also a useful input type when an output is required to to follow the 'Keybox' type input.

Medical

Medical

This is a 24 hour type input it will activate the external sounder and report a CID event 100.

Final Exit 2

Entry Delay 2

Any input programmed as ‘Final Exit 2’ will act as input type 'Final Exit', but the associated input will use ‘Entry Time 2’ rather than ‘Entry Time 1’ (programmed in Change Timers). This gives the opportunity to set different entry times for different entry routes.

 

 

 

 

 

Letter Selection

Email Enquiry

选择词条 邮件咨询